Dry Riser

What is a Dry Riser system?

A Dry Riser is a system that will allow firefighters to pump water, via an external connection, through the building's pipework to reach the landing valves. A dry riser has a landing valve on each floor. These can be opened, with the help of a wheel, to allow the arrival of water and fight the fire on the floor concerned.

According to the BS9990:2015 code of practice dry riser systems must be visually inspected every 6 months to ensure there has been no theft or vandalism on the system. An annual wet pressure test must be carried out every 12 months to ensure the dry riser doesn't have leaks or damaged components.

Our Dry Riser Servicing Includes

              All servicing is carried out in line with current British Standards and fire safety guidance, and typically includes:

​​

1. Visual inspection of the entire dry riser system​

2. Checking inlet breeching valves and landing valves​

3. Annual pressure testing of the system to 12 Bar for 15 mins.

4. Inspection of pipework, cabinets, valves, and caps.

5. Verification of signage and accessibility

6. Identification of leaks, corrosion, or damage

7. Issue of detailed service reports and certification

Why Choose us?

  • Experienced fire safety engineers​

  • Fully compliant with current standards and regulations

  • Minimal disruption to occupants and building operations

  • Clear, professional documentation for audits and insurers

  • Reliable, responsive, and safety-focused service

​We work closely with building owners, managing agents, and facilities managers to deliver dependable dry riser maintenance you can trust.